The
emergency lighting system should be regularly tested as follows.
|
|
Daily – Check
all lamps in a maintained system are lit. Record any faults in the
logbook and detail action taken.
|
|
Monthly –
Energise each emergency light from its battery by simulation of a
failure of the supply to the normal lighting for a period sufficient
only to ensure each lamp is illuminated. Record any faults in the
logbook and detail action taken.
|
|
Six Monthly -
Energise each emergency light from its battery by simulation of a
failure of the supply to the normal lighting for a period of 1 hour.
During this period the all luminaries and/or signs should be
examined to ensure that they are functioning correctly. Record any
faults in the logbook and detail action taken.
|
|
Yearly
- Energise each emergency light from its battery by
simulation of a failure of the supply to the normal lighting for a
period of its full duration. During this period the all luminaries
and/or signs should be examined to ensure that they are functioning
correctly. Record any faults in the logbook and detail action taken.
|
|
Check
each emergency lighting installation for compliance.
|
|
Appendix
11:
|
|
Emergency Lighting Log Book |
|
|
|

|
41 |

|
|
|
|